System 5000
Press Control
AUTO SETUP
MODULE
COLOR DISPLAY
OPERATING MANUAL
VERSION 1.1
LINK ELECTRIC & SAFETY CONTROL COMPANY
444 McNALLY DRIVE, NASHVILLE TN 37211
PH (615)-833-4168 FAX (615)-834-1984
Zobrazit stránku 0
1 2 3 4 5 6 ... 76 77

Shrnutí obsahu

Strany 1 - Press Control

System 5000Press ControlAUTO SETUPMODULECOLOR DISPLAYOPERATING MANUALVERSION 1.1LINK ELECTRIC & SAFETY CONTROL COMPANY444 McNALLY DRIVE, NASHV

Strany 2

April 12, 2012 Manual Version 1.12.4The example above can be taken one additional step if two press operators are given different usernames and differ

Strany 3 - Table of Contents

April 12, 2012 Manual Version 1.12.5SPMSPM00OrderCounterPC STATUSREADY TO STROKECounter OFFAutoSetupCHANGENUMBERSPMSPM00OrderCounterPC STATUSREADY TO

Strany 4

April 12, 2012 Manual Version 1.12.6Step A: Select the restricted item. In the example shown in Figure 2.2 the restricted item is SlideAdjust #1 set

Strany 5

April 12, 2012 Manual Version 1.13.1NOTE: NEVER remove or install any card in the OmniLink 5000 when the power to thecontrol is on. Doing so can dama

Strany 6

April 12, 2012 Manual Version 1.13.2Figure 3.2: Type “A” Valve ConfigurationFigure 3.3: Type “B” Valve ConfigurationSection 3.2 Valve SystemsCounterba

Strany 7

April 12, 2012 Manual Version 1.13.3Figure 3.4: Type “C” Valve ConfigurationFigure 3.5: Typical Counterbalance SystemType “C” An integrated Fill/Dump

Strany 8

April 12, 2012 Manual Version 1.13.4Figure 3.6: Auto-Counterbalance with Type “A” Integrated Valve.Figure 3.7: Auto-Counterbalance with Type “C” Integ

Strany 9

April 12, 2012 Manual Version 1.13.5Figure 3.8: Acceptable Locations for Mounting Counterbalance PressureTransducer.Section 3.3.1 Counterbalance Press

Strany 10

April 12, 2012 Manual Version 1.13.6Figure 3.9: Typical Standard Cushion SystemFigure 3.10: Cushion System with Type “B” IntegratedValve.Section 3.3.2

Strany 11

April 12, 2012 Manual Version 1.13.7Figure 3.11: Acceptable Locations for Mounting CushionPressure Transducer.Section 3.4.1 Cushion Pressure Transduce

Strany 13

April 12, 2012 Manual Version 1.13.8control came configured for a cushion adjust system, then a wiring diagram should have been providedas part of the

Strany 14

April 12, 2012 Manual Version 1.13.9NOTE: The cable should remain unbroken except for the connector in this junction box tokeep the shield integrity -

Strany 15

April 12, 2012 Manual Version 1.13.10NOTE: Balluff liner transducers with low profile housing and captive magnet have twospecial mounting instructions

Strany 16

April 12, 2012 Manual Version 1.14.1NOTE! An access code is required to reach the configuration menus of theOmniLink 5000 press control. The code is

Strany 17

April 12, 2012 Manual Version 1.14.2StrokeModeSingle StrokeDriveSpeedStrokeSpeedSPMSPM00OrderCounterPC STATUSCounter OFFAutoSetsEXIT00Program/Run Swit

Strany 18

April 12, 2012 Manual Version 1.14.3parameter is currently selected. Softkey 1 (the uppermost vertical softkey) will change its descriptionbased on t

Strany 19

April 12, 2012 Manual Version 1.14.4For hydraulic overloads this value should be the pressure specified by the pressmanufacturer for rated tonnage ope

Strany 20

April 12, 2012 Manual Version 1.14.5tons were stored for a job and the display unit is changed to pounds, when the jobis recalled it will be set to 40

Strany 21

April 12, 2012 Manual Version 1.14.6is recalled it will be set to 4000 pounds.Fault Time If the pressure in a counterbalance, cushion, or hydraulic o

Strany 22

April 12, 2012 Manual Version 1.14.7a) Go to the “Auto Sets” screen. This screen is reached by pressing the “AUTO SETS” softkey inthe Main Menu or Pr

Strany 23

April 12, 2012 Manual Version 1.1iTable of Contents Section 1 Introduction ... 1.1Section 1.1

Strany 24

April 12, 2012 Manual Version 1.14.8Slide Slot Corresponds to the physical slot number (SS1 in the example of Figure 4.3)selected for configuration on

Strany 25

April 12, 2012 Manual Version 1.14.9While the automatic slide adjust system will normally make its initial adjustmentto within .001" (.02mm) of t

Strany 26

April 12, 2012 Manual Version 1.14.10WARNING! Since the slide adjust configuration procedure requires measurement ofthe space between the press slide

Strany 27

April 12, 2012 Manual Version 1.14.11WARNING: After calibration always check for proper operation of the slide adjustsystem as wiring or transducer fa

Strany 28

April 12, 2012 Manual Version 1.14.12NOTE: It is very important to make as accurate a measurement as possible for theUpper and Lower Calibration Point

Strany 29

April 12, 2012 Manual Version 1.14.13WARNING: After calibration always check for proper operation of the slide adjustsystem as wiring or transducer fa

Strany 31

April 12, 2012 Manual Version 1.15.1StrokeModeSingle StrokeDriveSpeedStrokeSpeedSPMSPM00OrderCounterPC STATUSCounter OFFAutoSetsEXIT00Program/Run Swit

Strany 32

April 12, 2012 Manual Version 1.15.2various sub-systems.c) Each configured sub-system has a fault message. Under normal conditions, this fault should

Strany 33

April 12, 2012 Manual Version 1.15.3will not be used for production operation setup. Note that this key is onlyavailable when the RUN/PROG keyed swit

Strany 34

April 12, 2012 Manual Version 1.1iiSection 5 Operation ... 5.1Section 5.1 Slide Adjust Operat

Strany 35

April 12, 2012 Manual Version 1.15.4Fault If the slide adjust system detects an error it will be reported on this line. A faultoccurs when a hardware

Strany 36

April 12, 2012 Manual Version 1.15.5NOTE! A counterbalance pressure that is far too low or far too high during any shut heightadjustment may place e

Strany 37

April 12, 2012 Manual Version 1.15.6Section 5.1.4 Slide Fault and StatusThe last fault and current status of the slide system are displayed for diagno

Strany 38

April 12, 2012 Manual Version 1.15.7Fault If the air system detects an error it will be reported on this line. A fault occurswhen a hardware or firmw

Strany 39

April 12, 2012 Manual Version 1.15.8The RUN/PROG key, a user code, or both may be required to change them. If a force setpoint isentered, the proper

Strany 40

April 12, 2012 Manual Version 1.16.1Section 6 Diagnostics - Fault and Status MessagesWhen the press control screen reports a stop condition that indic

Strany 41

April 12, 2012 Manual Version 1.16.2This could be a bad connection to the fill valve, a failed fill valve, or no plantair pressure. Probably the most

Strany 42

April 12, 2012 Manual Version 1.16.3Hyd Overload Tripped The hydraulic overload operation screen will display this message when thepress hydraulic ove

Strany 43

April 12, 2012 Manual Version 1.16.4unplugged connector, failed power supply, failed transducer, or option board(5000-10B) problem. For rotary slide s

Strany 44

April 12, 2012 Manual Version 1.16.5shown if the position transducer is still functioning correctly.Waiting for Cntr-Bal The slide adjust system is wa

Strany 45

April 12, 2012 Manual Version 1.11.1Section 1 IntroductionThe 5000-10 Auto-Setup Module (ASM) allows the OmniLink 5000 Press and Automation control t

Strany 47

April 12, 2012 Manual Version 1.1A.1Appendix A Configuration ExamplesThis section of the manual will go though an example setup of each kind of system

Strany 48

April 12, 2012 Manual Version 1.1A.2supported units. The units can be pounds, kilograms, tons, or metric tons. We are using pounds. Notethat the un

Strany 49

April 12, 2012 Manual Version 1.1A.3currently in the cushion system.Next we move the editing cursor to the “Maximum Pressure” line. Since we found ea

Strany 50

April 12, 2012 Manual Version 1.1A.4Now we go to the “Auto Sets” screen and with the RUN/PROG switch in PROG hit the “CONFIGURE”softkey. After typing

Strany 51

April 12, 2012 Manual Version 1.1A.5some information needs to be gathered. A GEMCO 952 series linear transducer is mounted on the press slide. From

Strany 52

April 12, 2012 Manual Version 1.1A.6inches.Now we take the press back to the top of the stroke. With the slide adjust switch on, “JOG UP” and“JOG DOW

Strany 53

April 12, 2012 Manual Version 1.1A.7See section 5.1 for further details on slide adjust operation.Section A.5 Example Rotary Slide Adjust Configuratio

Strany 54

April 12, 2012 Manual Version 1.1A.8Now we take the press back to the top of the stroke. With the slide adjust switch on, “JOG UP” and“JOG DOWN” soft

Strany 55

April 12, 2012 Manual Version 1.1B.1Figure B.1: Typical Counterbalance Wiring Diagram.Appendix B Typical Wiring Diagrams

Strany 56

April 12, 2012 Manual Version 1.11.2Section 1.3 Shut Height ControlWhen a linear or rotary shut height control module is provided, the OmniLink 5000 c

Strany 57

April 12, 2012 Manual Version 1.1B.2Figure B.2: Typical Cushion Wiring Diagram.

Strany 58

April 12, 2012 Manual Version 1.1B.3Figure B.3: Conceptual Dual Resolver Mounting.

Strany 59

April 12, 2012 Manual Version 1.1B.4Figure B.4: Typical AMCI Dual Resolver Wiring Diagram.

Strany 60

April 12, 2012 Manual Version 1.1B.5Figure B.5: Typical GEMCO Dual Resolver Wiring Diagram

Strany 61

April 12, 2012 Manual Version 1.1B.6Figure B.6: Conceptual Linear Transducer Mounting

Strany 62

April 12, 2012 Manual Version 1.1B.7Figure B.7: Typical GEMCO Linear Transducer Wiring

Strany 63

April 12, 2012 Manual Version 1.1B.8Figure B.8: Typical MTS Temposonics II Linear Transducer Wiring

Strany 64

April 12, 2012 Manual Version 1.1B.9Figure B.8A: Typical Balluff Linear Transducer Wiring

Strany 65

April 12, 2012 Manual Version 1.1B.10Figure B.9: Typical Slide Motor Starter Wiring With Auxiliary ContactorFigure B.10: Typical Slide Motor Starter W

Strany 66

April 12, 2012 Manual Version 1.1C.1Figure C.1: Logic Module Firmware Chip LocationsAppendix C Installation Of OmniLink 5000 FirmwareFirmware for the

Strany 67

April 12, 2012 Manual Version 1.12.1Section 2 Parameter Entry and Access ControlSection 2.1 Parameter EntryThroughout the OmniLink control, a fairly s

Strany 69

April 12, 2012 Manual Version 1.1D.1Note! Step 1 MUST be done even if a LOX valve is opened in step 2 since thecontrol may try to pressurize the syste

Strany 70

April 12, 2012 Manual Version 1.1D.2Note! Step 1 MUST be done even if a LOX valve is opened in step 2 since thecontrol may try to pressurize the syste

Strany 71

April 12, 2012 Manual Version 1.1E.1Appendix E Configuration SheetsSection E.1 Air System Calibration SheetsAir PressureConfigurationAir Pressure Conf

Strany 72

April 12, 2012 Manual Version 1.1E.2Air PressureConfigurationAir Pressure Configuration Slot #4 Board ___________________________Name ___

Strany 73

April 12, 2012 Manual Version 1.1E.3Section E.2 Shut height Calibration Sheets Linear TransducerSlide ConfigurationSlide Configuration Slo

Strany 74

April 12, 2012 Manual Version 1.1E.4Rotary TransducerSlide ConfigurationSlide Configuration Slot #1 Board Rotary TransducerName _________

Strany 75

April 12, 2012 Manual Version 1.1F.1Appendix F SpecificationsSection F.1 5000-10A Pressure Control BoardAC Output Relays: Voltage: 120VACCurrent: 1Amp

Strany 76

April 12, 2012 Manual Version 1.12.2LOWERCASEUPPERCASETEXTENTRYABORTEDITCURSORLEFTCURSORRIGHTSPACESELECTLETTEREXITABCDEFGHIJKLMNOPQRSTUVWXYZ.+-=()%<

Strany 77

April 12, 2012 Manual Version 1.12.3Section 2.2 Access ControlThe OmniLink control has several parameters or operations that have limited access. In